Power Factor Correction: Why One Machine Needs Capacitors and the Other Doesn’t

Mi550 Wave Recording

By Johann Fritz • 2026-10-12

Last month a machine builder rented one of our Mi550 loggers to measure two tube-bending machines at a customer’s plant. One hour on the first machine, three hours on the second, then they emailed me the exports and asked a simple question: can you tell us what this means?

I get versions of that question every week, so I thought I’d walk through this one properly. Both machines had a poor power factor. That’s where the similarity ends. The causes were different, the fixes are different, and if the customer had just bolted a capacitor bank onto both of them, one would have got worse. Names and site are left out, the numbers are exactly as measured.

What was measured

A Meatrol Mi550 three-phase energy logger in three-phase four-wire mode with four current clamps, logging every five seconds. Each row of the export carries the five-second average of voltage, current, active, reactive and apparent power, both power factors, THD, the lot, plus the maximum and minimum inside the interval. The maximum channels matter here, because a bending stroke or a motor start is over in a second and the five-second average smooths it away.

Before I trust a single number from a clamp-on measurement I check the wiring from the data itself. The voltage angles of L2 and L3 should sit at 240° and 120° relative to L1. The voltage-to-current angle on each phase should be roughly the same as the other two. No phase should show negative active power on its own. Both logs passed cleanly. That check takes two minutes and it is the difference between a report and a guess. If a clamp is on the wrong conductor the power factor you calculate is fiction.

The supply itself was unremarkable in both cases: 230 to 238 V, unbalance under 0.7 %, neutral current never above 5 A. So the story is entirely about what the machines do with the current, not about the grid.

Machine A: the hydraulic bending cell

Active and reactive power of a hydraulic bending cell over three hours: reactive power stays flat at about 26 kvar while active power swings, the signature of a continuously running under-loaded motor and a poor power factor
Machine A: active and reactive power, 5-second averages

Machine A is a hydraulic bending cell with a continuously running pump. It was in production for 68 % of the three hours and idle for 28 %. It used 42.6 kWh, which works out at 14 kW averaged across the whole log, or about 20 kW while actually running. Peaks reached 62 kW on a five-second average.

The thing to look at in the chart is the orange line. Reactive power barely moves while the cell is running: about 23 kvar when only the pump is turning over (blue line at 13 to 15 kW), 26 to 27 kvar during normal bending (blue at 16 to 25 kW), and 28 to 30 kvar on the heaviest strokes (the blue spikes to 45 kW). Active power swings by a factor of three; reactive power moves by a quarter. That is the signature of an induction motor that runs all the time and is loaded only some of the time. Most of the magnetising current is there whether the motor does work or not.

Power factor in production: 0.55. The displacement power factor, which is the cosine of the angle between the fundamental voltage and current, came out at 0.57. Those two numbers being almost equal tells you the current waveform is clean and the whole problem is phase shift. Current THD was a moderate 16 %.

Over three hours the cell drew 54 kvarh of lagging reactive energy against 43 kWh of active energy. That is a ratio of 1.27. German utilities typically bill reactive energy above 50 % of active energy (which corresponds to a power factor of 0.9), so if this cell runs shifts and is a big share of the site, it is almost certainly on the bill already.

One more thing the max channels showed: about fifteen direct-on-line starts of the pump motor, each pulling 180 to 205 A for a couple of seconds against a running current of 45 A. Every time the cell came back from an idle pause.

Machine B: the servo bending machine

Active and reactive power of a servo-driven bending machine over one hour: active power spikes with each stroke while reactive power is small when running and about 5 kvar capacitive at idle
Machine B: active and reactive power, 5-second averages

Machine B is a different design. No continuously running pump. The active power jumps from almost nothing to 15 to 33 kW with every stroke and drops straight back. It was running 38 % of the hour, idle 37 %, and used only 3.8 kWh.

In production the power factor was 0.84, with a displacement power factor of 0.90. Now the two numbers are far apart, and that gap is the whole point. The fundamental current is only 26° out of phase, which is fine. The missing 0.06 is harmonic current: THD on the current ran at 30 to 90 % during strokes, with a K-factor up to 5. That’s what frequency converters and servo drives do. They rectify the mains into a DC bus and pull current in short pulses near the voltage peaks.

The odd finding was the idle state. Switched on but doing nothing, Machine B draws 8 A on every phase for 0.4 kW of real power. The current leads the voltage by nearly 90°. That is 5 kvar of pure capacitive load, sitting on the supply the whole time the machine is on. It is either a fixed capacitor bank wired straight to the incomer or the line filters on the drives, and only the machine documentation can say which.

Total power factor and displacement power factor of a servo bending machine over one hour: the gap between the two lines is harmonic distortion from the drives, which capacitors cannot correct
Machine B: total power factor and displacement power factor

Why the two numbers matter

Every network analyser worth its price reports two power factors, and most people only look at one.

The total power factor, usually written λ, is active power divided by apparent power. It includes everything that makes the current bigger than it needs to be: phase shift and harmonic distortion together.

The displacement power factor, cos φ, looks only at the 50 Hz fundamental. It ignores harmonics.

λ can never be higher than cos φ. When they’re nearly equal, as on Machine A, the current is a clean sine wave and the loss is phase shift. That is exactly what capacitors correct. When λ is well below cos φ, as on Machine B, the gap is harmonic current. Capacitors don’t fix harmonics. Worse, a plain capacitor bank in parallel with a drive full of harmonics is a classic resonance setup and can amplify the very currents you’re trying to get rid of.

If you only read one number off your meter, you cannot tell these two situations apart. If you read both, the diagnosis is a one-line calculation. I wrote up the maths in how to calculate power factor if you want the long version.

For Machine A, the fix is standard. To get from 0.55 to 0.95 at 20 kW you need about 20 kvar of compensation (the maths: at cos φ 0.95 the allowable reactive power is 20 × tan(acos 0.95) = 6.6 kvar; measured was 26; the difference is the bank). Running current drops from about 45 A per phase to about 30 A. Two details matter. The bank has to be switched with the pump contactor, because at idle the cell flips to slightly capacitive and a permanently connected 20 kvar would over-compensate badly every time it pauses. And it should be a detuned bank with series reactors, because there are drives on the same site.

For Machine B, no capacitors. The power factor under load is acceptable, and what’s left is harmonics that only an active filter or line reactors would improve. At 30 % current THD and under 1.5 % voltage THD I wouldn’t bother. The thing worth doing is finding out what that 5 kvar capacitive idle load is, and whether it can be switched with the drives instead of sitting on the mains permanently. It costs nothing on the bill, but a leading load can confuse a central compensation controller and it’s one half of a resonant circuit.

What a one-hour log can and can’t tell you

The honest limits. This is one afternoon on two machines. It describes what the machines do with great confidence and says nothing about weekly profiles or how much of the site’s reactive energy they account for. The obvious next measurement is a week at the main incomer. That turns “probably on the bill” into a number. For measurements over several days or weeks, portable energy loggers can capture load profiles, peak demand and power factor throughout normal operating cycles.

But it also shows what you get from a rented clamp-on logger and an afternoon. Two machines nobody had measured, two different problems, one concrete sizing and one “go and look in the cabinet”. None of it was visible on the electricity bill, which only ever shows the total. Beyond power factor correction, energy logging can also reveal peak demand and unnecessary energy consumption. Read more about how energy logging can save you time and money

To measure is to know.

Frequently asked questions

Above 0.9 is the usual target, and in Germany it’s the point where reactive energy starts being billed. Above 0.95 is good practice. A continuously running motor that is only intermittently loaded will typically sit between 0.5 and 0.7 without correction.

Only if the cause is phase shift (inductive load). Compare the total power factor with the displacement power factor on your meter. If they’re close, capacitors work. If the total is much lower than the displacement value, the cause is harmonic distortion and capacitors won’t help; a detuned bank or an active filter is needed.

Usually one of three things: a motor that keeps running (inductive, lagging), a fixed capacitor bank or EMC filters that stay live (capacitive, leading), or control electronics. A logger shows which, because the sign of the reactive power tells you lead from lag.

Long enough to cover the duty cycle you care about. One or two hours is enough to characterise a single machine’s behaviour, as here. To size compensation for a whole site or to argue with a utility bill, log the incomer for at least a week.